| Item |
Test condition/Methods |
Standard |
Performance |
| Time/Current |
100% of current rating |
IEC 60269/UL248-19 |
No Fusing;4 hours Min. |
| 113% of current rating *IEC |
IEC 60269 |
60 Minutes Min. |
| 145% of current rating *IEC |
IEC 60269 |
60 Minutes Max. |
| 105% of current rating *UL |
UL-248.19 |
60 Minutes Min. |
| 135% of current rating *UL |
UL-248.19 |
60 Minutes Max. |
| 200% of current rating |
IEC 60269/UL248-19;1-30A |
4 Minutes Max. |
| IEC 60269/UL248-19;31-60A |
6 Minutes Max. |
| Endurance Test |
100% of rating current for 4 hours and testing Temperature rise at the last 5min. |
IEC 60269-6 UL248-19 |
≤65K |